Following is a list of measures offered and the corresponding incentive rate on a per unit basis. Please refer to the terms and conditions for specific requirements of each measure.
| Measure | Incentive Rate |
| Auto Closer | |
| Auto-Closers for Main Cooler Doors | $40.00/closer |
| Auto-Closers for Main Freezer Doors | $50.00/closer |
| Auto-Closers for Reach-In Cooler Doors | $40.00/closer |
| Auto-Closers for Reach-In Freezer Doors | $50.00/closer |
| Evaporator Fans Controller for Walk-in Coolers | $75.00/controller |
| Door Gaskets on Solid Doors for Coolers or Freezers | |
| Refrigerator/Freezer Door Gaskets - Solid Door | $4.00/linear ft. |
| Refrigerator/Freezer Door Gaskets - Glass Door | $4.00/linear ft. |
| Insulation for Bare Suction Lines | $1.00/linear ft. |
| Night Covers for Open Vertical and Horizontal Display Cases | |
| Medium Temperature Case | $9.00/linear ft. |
| Low Temperature Case | $9.00/linear ft. |
| Strip Curtains for Walk-In Boxes | $3.00/square ft. |
| Vending Machine Controller | $90.00/controller |
| Anti-Sweat Heater (ASH) Controls | $14.00/linear ft. |
| Efficient Evaporator Fan Motor Electronically Commutated Motor (ECM) | $20.00/motor |
| Efficient Evaporator Fan Motor Permanent Split Capacitor (PSC) Motor | $20.00/motor |
| Special Doors with Low/No Anti-Sweat Heat on Low Temp Display Cases | $50.00/door |
| New Refrigeration Display Case with Doors Low Temperature Case | $200.00/linear ft. |
| New Refrigeration Display Case with Doors Medium Temperature Case | $150.00/linear ft. |
Auto-Closers for Main Cooler or Main Freezer Doors and Reach-In Cooler or Freezer
The auto-closer should be applied to the main insulated opaque door(s) of a walk-in cooler or freezer and reach-in cooler or freezer. The auto-closer must be able to firmly close that door when it is within one inch of full closure.
Evaporator Fan Controller for Walk-in Coolers
Must reduce airflow of evaporator fans in medium-temperature walk-in coolers when compressor(s) cycle off and there is no refrigerant flow through the evaporator. Must control a minimum fan load of 1/20 horsepower where the fan(s) operate continuously at full speed. Must reduce fan motor power by at least 75% during the compressor off-cycle.
Not eligibleif any of the following conditions apply:
Door Gaskets on Solid Doors
Must replace a worn gasket on the insulated opaque door of a walk-in or reach-in cooler or freezer. Replacement gaskets must meet the manufacturer's installation specifications, specifically regarding dimensions, materials, attachment method, style, compression, and magnetism. Incentive is based on total door perimeter in linear feet.
Door Gaskets on Glass Doors
Must replace a worn gasket on a reach-in glass door(s) of a cooler or freezer. Replacement gaskets must meet the manufacturer's installation specifications, specifically regarding dimensions, materials, attachment method, style, compression, and magnetism. Incentive is based on total door perimeter in linear feet.
Insulation for Bare Suction Lines
Must insulate bare refrigeration suction lines of 1 5/8 inches or less on existing equipment only. Medium temperature lines require 3/4-inch of flexible closed-cell nitrite rubber, or equivalent insulation, and low temperature lines require 1-inch of the same insulation. Insulation exposed to outside weather must be jacketed (such as with a medium-gauge aluminum jacket) or protected from the weather in some way. Incentive is based on the length, in linear feet, of the insulation installed.
Night Covers for Open Vertical and Horizontal Display Cases
Must install a cover on an otherwise open display case to decrease cooling load of the refrigerated case during off hours. The incentive is based on the linear footage of the installed night cover. It is recommended that these film type covers have small, perforated holes to decrease moisture buildup. The cover must be applied for a period of at least six hours in a 24-hour period. Customer should consider the following: using proper compressor capacity modulation mechanisms (such as variable speed drive (VSD) or cylinder un-loader); using evaporator pressure regulator (EPR) and possibly resetting to higher suction temperatures when shields are applied; resizing TVX and resetting suction pressure to a higher value. Consult with the case manufacturer or an authorized representative to determine if installing night covers will impact system performance.
Strip Curtains for Walk-in Boxes
Must install new strip curtains or plastic swinging doors on doorways of walk-in boxes and refrigerated warehouses. This incentive is not available for replacement of existing strip curtains that have useful life left. Incentive is based on the square footage of the doorway.
Vending Machine Controller
Intended for refrigerated vending machines containing only non-perishable bottled and canned beverages. Controller must include a passive infrared occupancy sensor to turn off fluorescent lights and compressor when surrounding area is unoccupied for 15 minutes or longer. Control logic should periodically power up machine at two-hour intervals to maintain product temperature and provide compressor protection. Refurbished vending machines that include this option are eligible.
Anti-Sweat Heat (ASH) Controls
Must install a device that senses the relative humidity in the air outside of the display case and reduces or turns off the glass door (if applicable) and frame anti-sweat heaters at low humidity conditions. Equivalent technologies that can reduce or turn off anti-sweat heater based on the amount of condensation formed on the inner glass pane may also qualify. This measure cannot be used in conjunction with New Refrigeration Display Case with Doors (Low and Medium Temperatures) and New High Efficiency Refrigeration Display Case with Special Doors (Low Temp) measures. Incentive is based on the total linear footage of the case.
Efficient Evaporator Fan Motor
Applicable to existing standard efficiency shaded pole evaporator fan motor of refrigerated display cases or fan coil systems in walk-ins. Shaded pole motors to be replaced by either electronically commutated motors (ECM) or permanent-split-capacitor (PSC) motors. This measure cannot be used in conjunction with Evaporator Fan Controller Measure for Walk-in Coolers.
Special Doors with Low/No Anti-Sweat Heat on Low Temperature Display Cases
Must replace an existing standard glass door of a low temperature reach-in display case with a special glass door that requires minimum to no anti-sweat heat (ASH). Doors must prevent condensation from occurring within the frame assembly. Total door rail, glass, and frame heater amperage (at 120 volts) cannot exceed 0.39 amps per foot of display case. Incentive is based on number of doors replaced. This measure cannot be used in conjunction with Anti-Sweat Heater (ASH) Controls measure.
New Refrigeration Display Case with Doors (Low and Medium Temperatures)
Must replace an existing open multi-deck display case with a new high efficiency reach-in unit with standard glass doors with electronically commutated motor (ECM) fan, T-8 lamps and electronic ballast. This measure can be applied to self-contained or remote cases. New display cases are incented based on their length. New case length must be equal to or shorter than original case. Deli Cases, Custom Coolers/Freezers, and Walk-in boxes with reach in doors do not qualify for this measure.
New High Efficiency Refrigeration Display Case with Special Doors (Low Temp)
A new high efficiency reach-in display case must replace an existing low temperature self-contained or remote reach-in as shown in the table below. This measure cannot be used in conjunction with Anti-Sweat Heater (ASH) Controls measure. Deli Cases, Custom Coolers/Freezers, and Walk-in boxes with reach in doors do not qualify for this measure.
| Existing | Replacement |
| T-12 lamps, magnetic ballast | T-8 lamps, electronic ballast |
| Shaded pole fan motor | ECM fan |
| Standard glass doors | Low/no anti-sweat glass double pane doors meeting the requirements of Special Doors
With Low/No Anti‑Sweat Heat on Low Temperature Display Cases Measure |